Power Agent Battery Monitoring System
A lead acid battery can be characterized by an equivalent circuit of three
resistances that limit its performance:
Power Agent Site Controller
Number of
Monitored Strings:
Number of Batteries
In Each String:
Total Batteries, All
Strings:
Network Interface:
Network Protocols:
Local Diagnostic
Interface:
Size:
Mounting:
Power:
Battery Monitoring System Components
The Power Agent BMS has three unique and advanced components.
Power Agent Systems LLC 589 Bethlehem Pike, Suite 1000, Montgomeryville, PA 18936 215.310.6243
|
PAS-PA-BMS-SC1
6 Max
100
240 max
Ethernet 10/100 Base T
TCIP/IP, UDP, HTTP, Telnet, SMTP, SNMP
Proprietary; 9600 baud, RJ-45, ASCII
6.0" x 9.0" x 1.6"
Rack or Wall
15-60VDC, 2W type (110/220 VAC power
pack available)
Power Agent Sensor
Model Number:
Parametric
Measurements:
Site Controller
Interface:
Mounting
Indicators:
Isolation:
Size:
Power:
PAS-PA-BSx-y-z
Total string voltage, battery voltage, post
temperature, dynamic resistance/admittance
2 (ea) low voltage RJ-45
Module mounts on battery negative terminal;
wire/lug connection to positive terminal
Red/Green LED
Optically isolated from controller
1.5" x 3.0" x 0.75"
Powered from monitored battery; 5.0 ma
average standby current
A current-limiting resistance (Relectrolyte) attributable to the
battery chemist
A current-limiting resistance (Rmetal) attributable to the internal
connections
A self-discharge resistance (Rleakage) which causes the
battery to lose charge even when no load is connected
"Admittance" is a composite measurement of all the battery's internal
resistances, including an apparent internal capacitance.
Each Power Agent BMS sensor generates a digitally synthesized
sinusoidal AC test signal (Itest) which is passes through the battery
terminals in order to measure the battery's admittance. A site controller
unit communicates with each o f the sensors to collect these admittance
measurements, along with battery voltage and post temperature.



Sensors: A sensor is attached to the posts of each monitored
battery. The sensors measure the battery's admittance (internal
resistance), voltage, and post temperature.
A Site Controller: The site controller communicates with each of
the sensors and collects the most recent measurement data. It
checks each measurement against locally stored alarm
thresholds and alerts the user's monitoring software is an
abnormality occurs. The site controller is fully Ethernet TCP/IP
compatible.
Standards-based SNMP interface, is the only battery monitoring
system that gives the user "freedom of choice" to select the
optimum software for the application. Our choices include:



Web Based / No software
The site controller's internal web pages are all that is
necessary for many users.
Lookout Software
Free Lookout software provided by Power Agent
Systems provides a global view of multiple installations
with the ability to "drill in" to details.
Continuity
Continuity SBL enterprise-class battery system
monitoring and analysis package.
Open Software
Any software that supports a SNMP interface.